核电厂辅助电源断相保护方案探讨

Discussion of Auxiliary Power Source Open-Phase Protection in Nuclear Power Plant

  • 摘要:
    目的 核电厂的辅助电源正常空载备用运行,发生单相断相后继电保护无法发出报警,但是断相运行对核安全构成严重的威胁,必须配置专用的断相保护。根据实际运行情况,断相保护除了考虑常规的近端断相外,还需要考虑远端断相和变压器中性点不接地的情况。
    方法 通过对核电厂辅助变压器(包括中性点不接地)在近端和远端断相后电压和电流的行为分析,找出电压、电流和零序阻抗等电气量在正常运行和故障运行的不同点,来设置断相保护。并对“华龙一号”核电机组的辅助电源进行分析,根据其特点推荐断相保护。
    结果 经过研究分析,核电厂辅助变压器在近端单相断线时三相电压不变,断相相电流为0,另两相电流增大,有零序电流,零序阻抗增大。在远端单相断相时,三相电压不变,三相电流增大且同相位,有零序电流。中性点不接地变压器单相断线时,断相相电压下降、断相相电流为0,有负序电流。断相保护可以依据这些电气量的变化来设置保护,主要有2种方案:中性点注入法依据断相后零序阻抗增大来设置保护,光CT 测量法依据断相后电流及其相位的变化来设置保护。
    结论 2种断相保护方案各有优缺点,都可以用于核电厂辅助电源的断相保护;对于“华龙一号”六机组核电基地全部建成后的二线路六变压器的辅助电源,推荐采用每台变压器配1套中性点注入法或者每台变压器配1套光CT测量法2种方案;如果是中性点不接地的变压器,推荐光CT测量法,带低电压和负序电流判据;保护出口投报警。

     

    Abstract:
    Objective The auxiliary power source in nuclear power plant operates at no-load normally, the protection cannot alarm when it occurs single phase open, but this open-phase condition will threaten the nuclear safety seriously, it should assemble special open-phase protection. Besides the near-end open-phase, the open-phase protection should consider the far-end open-phase and neutral ungrounded.
    Method Based on the analysis of voltage and current behavior of the auxiliary transformer in nuclear power plant during the near-end open-phase and far-end open-phase failure, the different points of voltage, current, and zero-sequence impedance in normal operation and fault operation were identified to set open-phase protection. And the auxiliary power source of "Hualong No. 1" nuclear power unit was analyzed, the open-phase protection was recommended according to its characteristics.
    Result After research and analysis, when the auxiliary transformer of nuclear power plant occurs single open-phase at near-end, the three-phase voltage is unchanged, the break phase current is zero and it has zero sequence current, the zero sequence impedance is increased. When it occurs single open-phase at far-end, the three-phase voltage is unchanged, the three-phase current is increased and in the same phase angle, also it has zero sequence current. when the neutral ungrounded transformer occurs single open-phase, the break phase voltage is drops, the break phase current is zero, and there is negative sequence current. Open-phase protection can use these electrical parameter changes to set protection, there are two main types, neutral injection method set protection with zero sequence impedance increase after open-phase, optical CT measurement method set protection with current and its phase change after open-phase.
    Conclusion Both of the schemes have their advantages and disadvantages, and both can be used for the open-phase protection of auxiliary power in nuclear power plant. For the auxiliary power source of two lines and six transformers after the completion of six-unit nuclear power base of "Hualong No. 1", it is recommended to adopt two schemes: one set of neutral injection method for each transformer or one set of optical CT measurement method for each transformer. If it is an ungrounded neutral transformer, it is recommended to use optical CT measurement method with low voltage and negative sequence current. All the protection are used for alarm.

     

/