HE Jian. Coordination of the Active Saturated Iron-core Superconductive Fault Current Limiters with Zero-sequence Current Protection of Transmission Lines[J]. SOUTHERN ENERGY CONSTRUCTION, 2015, 2(S1): 30-34. doi: 10.16516/j.gedi.issn2095-8676.2015.S1.007
Citation: HE Jian. Coordination of the Active Saturated Iron-core Superconductive Fault Current Limiters with Zero-sequence Current Protection of Transmission Lines[J]. SOUTHERN ENERGY CONSTRUCTION, 2015, 2(S1): 30-34. doi: 10.16516/j.gedi.issn2095-8676.2015.S1.007

Coordination of the Active Saturated Iron-core Superconductive Fault Current Limiters with Zero-sequence Current Protection of Transmission Lines

doi: 10.16516/j.gedi.issn2095-8676.2015.S1.007
  • Received Date: 2015-11-01
  • A 500 kV Saturated Iron-core Superconductive Fault Current Limiter (SISFCL) has been designed to be installed in an EHV transmission system in southern China. We carried out studies on compatibility and coordination problems in the application of this kind of device in an EHV network. In this paper, the operational principle of an SISFCL and the protection configuration of transmission lines are briefly introduced. The influence of an SISFCL on the zero-sequence current protection of the grid, taking into consideration both the fault of SISFCL itself and fault of the power lines, is discussed. In order to coordinate the SISFCL and the grid protection scheme, requirements and recommendations are proposed. A model of a 500 kV double-circuit transmission system with SISFCLs is built using Electromagnetic Transient Program including DC (EMTDC) software package. The simulation results are in good agreement with the theoretical analyses.
  • 通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

Article Metrics

Article views(142) PDF downloads(16) Cited by()

Related

Coordination of the Active Saturated Iron-core Superconductive Fault Current Limiters with Zero-sequence Current Protection of Transmission Lines

doi: 10.16516/j.gedi.issn2095-8676.2015.S1.007

Abstract: A 500 kV Saturated Iron-core Superconductive Fault Current Limiter (SISFCL) has been designed to be installed in an EHV transmission system in southern China. We carried out studies on compatibility and coordination problems in the application of this kind of device in an EHV network. In this paper, the operational principle of an SISFCL and the protection configuration of transmission lines are briefly introduced. The influence of an SISFCL on the zero-sequence current protection of the grid, taking into consideration both the fault of SISFCL itself and fault of the power lines, is discussed. In order to coordinate the SISFCL and the grid protection scheme, requirements and recommendations are proposed. A model of a 500 kV double-circuit transmission system with SISFCLs is built using Electromagnetic Transient Program including DC (EMTDC) software package. The simulation results are in good agreement with the theoretical analyses.