DENG Chenggang, SHI Jia. Terminal Temperature Difference Value Analysis of High Pressure Heater for 1 000 MW Ultra-supercritical Coal-fired Unit[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 14-17. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.004
Citation: DENG Chenggang, SHI Jia. Terminal Temperature Difference Value Analysis of High Pressure Heater for 1 000 MW Ultra-supercritical Coal-fired Unit[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 14-17. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.004

Terminal Temperature Difference Value Analysis of High Pressure Heater for 1 000 MW Ultra-supercritical Coal-fired Unit

doi: 10.16516/j.gedi.issn2095-8676.2016.S1.004
  • Received Date: 2015-10-30
  • Publish Date: 2020-07-17
  • In this article, based on the heat balance diagram of 1 000 MW ultra-supercritical coal-fired unit, through calculating &analyzing the influence of HP heater superheated steam cooling section outlet design temperature on HP heater heat transfer area and HP heater upper terminal difference; and influence of HP heater terminal difference(upper/lower) on heat transfer area, unit heat consumption value, has presented the HP heater upper terminal difference should not be set to -2℃ according to the specification, but determined by calculation on specific project conditions, and has provided reference for energy conservation of power units.
  • 通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

Article Metrics

Article views(244) PDF downloads(98) Cited by()

Related

Terminal Temperature Difference Value Analysis of High Pressure Heater for 1 000 MW Ultra-supercritical Coal-fired Unit

doi: 10.16516/j.gedi.issn2095-8676.2016.S1.004

Abstract: In this article, based on the heat balance diagram of 1 000 MW ultra-supercritical coal-fired unit, through calculating &analyzing the influence of HP heater superheated steam cooling section outlet design temperature on HP heater heat transfer area and HP heater upper terminal difference; and influence of HP heater terminal difference(upper/lower) on heat transfer area, unit heat consumption value, has presented the HP heater upper terminal difference should not be set to -2℃ according to the specification, but determined by calculation on specific project conditions, and has provided reference for energy conservation of power units.

DENG Chenggang, SHI Jia. Terminal Temperature Difference Value Analysis of High Pressure Heater for 1 000 MW Ultra-supercritical Coal-fired Unit[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 14-17. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.004
Citation: DENG Chenggang, SHI Jia. Terminal Temperature Difference Value Analysis of High Pressure Heater for 1 000 MW Ultra-supercritical Coal-fired Unit[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 14-17. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.004

Catalog

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return